Telephone: +254 20 8000175/6

Mobile: +254 720 635153, +254 736 099227

TROJAN SPRE 06 415 (L-16-RE-B) SOLAR PREMIUM LINE FLOODED BATTERY

Weight54kg
TypeSPRE 06 415
Voltage6 Volts
Ampere Hour Capacity (5-Hr Rate)303AH
Ampere Hour Capacity (20-Hr Rate)370AH
Ampere Hour Capacity (100-Hr Rate)415AH
Energy (100-Hr Rate)2.46kWh
Dimensions295x178x450mm
More Details... Make an Inquiry

$360.00

 

BATTERY:  Deep-Cycle Flooded/Advanced Lead Acid Battery

COLOR Maroon

WATERING Single-Point Watering Kit (Optional)

PRODUCT HIGHLIGHTS Smart Carbon™ for Improved Performance 8 Years Battery Life Based on IEC 61427

Product Enquiry
Contact Form

Description

Model Terminal Type D   Dimensions B Inches (mm)   Weight E Lbs. (kg) HydroLink or SPWK Handles
SPRE 06 255 16 Length Width Height C 67 (30) SPWK Embedded
10.30 (262) 7.13 (181) 11.74 (298)

ELECTRICAL SPECIFICATIONS

 Voltage      Capacity A Amp-Hours (Ah)     Energy (kWh)
  10-Hr 20-Hr 48-Hr 72-Hr 100-Hr 100-Hr
6V 211 229 244 249 255 1.53

CHARGING INSTRUCTIONS

Charger Voltage Settings (at 77°F/25°C)    
System Voltage 6V 12V   24V 48V
Maximum Charge Current (% of C20 Rate)* 13%    
Maximum Absorption Phase Time (hours) 4    
Absorption Voltage ** 7.35 14.70   29.40 58.80
Float Voltage 6.75 13.50   27.00 54.00
Equalization Voltage 8.10 16.20   32.40 64.80
Do not install or charge batteries in a sealed or non-ventilated compartment. Constant under or overcharging will damage the battery and shorten its life as with any battery. *If charging time is limited contact Trojan Technical Support for assistance.

**In cases where controller has a bulk voltage setting, use absorption voltage setting above.

   

Designed in compliance with applicable

BCI, DIN, BS and IEC standards. Tested in compliance to BCI and IEC standards.

CHARGING TEMPERATURE COMPENSATION                        STATE OF CHARGE MEASURE OF OPEN-CIRCUIT VOLTAGE

Percentage Charge Specific Gravity Cell 6-Volt
100 1.277 2.122 6.37
90 1.258 2.103 6.31
80 1.238 2.083 6.25
70 1.217 2.062 6.19
60 1.195 2.040 6.12
50 1.172 2.017 6.05
40 1.148 1.993 5.98
30 1.124 1.969 5.91
20 1.098 1.943 5.83
10 1.073 1.918 5.75
Add Subtract
0.005 volt per cell for every 1°C below 25°C

0.0028 volt per cell for every 1°F below 77°F

0.005 volt per cell for every 1°C above 25°C

0.0028 volt per cell for every 1°F above 77°F

Operating Temperature Self Discharge
-4°F to 113°F (-20°C to +45°C). At temperatures below 32°F (0°C) maintain a state of charge greater than 60%. 5 – 15% per month depending on storage temperature conditions.

OPERATIONAL DATA

PERCENT CAPACITY VS. TEMPERATURE

     DOD VS CYCLE LIFE IN A STATIONARY APPLICATION

SELF DISCHARGE VS. TIME*                                                     

*PERIODIC CHARGE

FREQUENCY
Provide a periodic freshening charge to maintain a SOC greater than the threshold of 70%.

DIMENSIONS INCHES (MM) - shown with SLT

10.30 (262) LENGTH

TERMINAL CONFIGURATIONSD

16 SLT Small L-Terminal
Terminal Height Inches (mm)

1.28 (32.5)

Torque Values: in-lb (Nm)

95 -105 (11 - 12)

Bolt Size

5/16"-18

 

EXPECTED LIFE VS. TEMPERATURE

 
Chemical reactions internal to the battery are driven by voltage and temperature. The higher the battery temperature, the faster chemical reactions will occur. While higher temperatures can provide improved discharge performance the increased rate of chemical reactions will result in a corresponding loss of battery life. As a rule of thumb, for every 10°C increase in temperature the reaction rate doubles. Thus, a month of operation at 35°C is equivalent in battery life to two months at 25°C. Heat is an enemy of all lead acid batteries, FLA, AGM and gel alike and even small increases in temperature will have a major influence on battery life.
  1. The amount of amp-hours (Ah) a battery can deliver when discharged at a constant rate at 86°F (30°C) and maintain a voltage above

1.75 V/cell. Capacities are based on peak performance.

  1. Dimensions may vary depending on type of handle or terminal. Batteries should be mounted with 0.5 inches (12.7 mm) spacing minimum.
 
Deep-cycle batteries used in off-grid and unstable grid applications are heavily cycled at partial state of charge (PSOC). Operating at PSOC on a regular basis can quickly diminish the overall life of a battery, which results in frequent and costly battery replacements. To address the impact of PSOC on deep-cycle batteries in renewable energy (RE), inverter backup and telecom applications, Trojan Battery has now included Smart Carbon™ as a standard feature in its Solar Industrial and Solar Premium flooded battery lines.