Telephone: +254 20 8000175/6

Mobile: +254 720 635153, +254 736 099227

TROJAN SIND 02 2450 DEEP-CYCLE BATTERY 2V 1882AH AT 20HR

More Details... Make an Inquiry

$816.00

MODEL :SIND 02 2450

VOLTAGE: 2V

CAPACITY: 2450Ah @ 100Hr

MATERIAL: Polypropylene (internal cell container) Polyethylene (outer container) BATTERY: Deep-Cycle Flooded/Advanced Lead Acid Battery

COLOR: Maroon

WATERING: Single-Point Watering Kit (Optional)

PRODUCT HIGHLIGHTS: Smart Carbon™ for Improved Performance 17 Years Battery Life Based on IEC 61427

Product Enquiry
Contact Form

Description

 Voltage Capacity A Amp-Hours (Ah) Energy (kWh)
10-Hr 20-Hr 48-Hr 72-Hr 100-Hr 100-Hr
2V 1712 1882 2166 2318 2450 4.90

CHARGING INSTRUCTIONS

Charger Voltage Settings (at 77°F/25°C)
System Voltage 6V 12V 24V 48V
Maximum Charge Current (% of C20 Rate)* 13%
Maximum Absorption Phase Time (hours) 4
Absorption Voltage ** 7.20 14.40 28.80 57.60
Float Voltage 6.75 13.50 27.00 54.00
Equalization Voltage 8.10 16.20 32.40 64.80
Do not install or charge batteries in a sealed or non-ventilated compartment. Constant under or overcharging will damage the battery and shorten its life as with any battery. *If charging time is limited contact Trojan Technical Support for assistance.

**In cases where controller has a bulk voltage setting, use absorption voltage setting above.

Designed in compliance with applicable

BCI, DIN, BS and IEC standards. Tested in compliance to BCI and IEC standards.

CHARGING TEMPERATURE COMPENSATION                        STATE OF CHARGE MEASURE OF OPEN-CIRCUIT VOLTAGE

Percentage Charge Specific Gravity Voltage
100 1.260 2.11
90 1.246 2.09
80 1.227 2.07
70 1.207 2.05
60 1.187 2.03
50 1.165 2.01
40 1.142 1.99
30 1.119 1.96
20 1.096 1.94
10 1.072 1.92
Add Subtract
0.005 volt per cell for every 1°C below 25°C

0.0028 volt per cell for every 1°F below 77°F

0.005 volt per cell for every 1°C above 25°C

0.0028 volt per cell for every 1°F above 77°F

Operating Temperature Self Discharge
-4°F to 122°F (-20°C to +50°C). At temperatures below 32°F (0°C) maintain a state of charge greater than 60%. 5 – 15% per month depending on storage temperature conditions.

OPERATIONAL DATA

PERCENT CAPACITY VS. TEMPERATURE

DOD VS CYCLE LIFE IN A STATIONARY APPLICATION